Plc control logic safety review

Skill Raishin/vanguard-frontier-agentic/skills/qa/plc-control-logic-safety-review

Use this skill when reviewing exported PLC program logic (Ladder Diagram, Structured Text, Function Block Diagram, or Sequential Function Chart) for safety and reliability defects. Trigger when a user provides exported IEC 61131-3 program source, an I/O list, a safety requirements spec, a SIL assessment, or asks whether their PLC logic has a safe state, a correct E-stop implementation, unresolved latches, forced I/O, or interlock bypass risks. This is OT/ICS — defects injure people or destroy equipment. The skill performs static review only; it never connects to a live PLC, never writes to a controller, and never advises modifying running logic or bypassing a safety function.From its SKILL.md

Install
npx -y skills add Raishin/vanguard-frontier-agentic --skill plc-control-logic-safety-review

Assembled from the repository path, not quoted from the project. Check it against their README if it does not work.

One thing to look at

  • 20 stars20 stars. Stars are a popularity signal and not a quality one, but at this level it is likely that nobody has read this closely except its author, and you would be relying on your own review.

SKILL.md

5.5 KB, 974 tokens by cl100k_base, as published. Nobody here has run it

PLC Control Logic Safety Review

Purpose

This skill statically reviews exported IEC 61131-3 PLC program logic for safety and reliability defects before that logic reaches a live controller. In operational technology (OT) and industrial control systems (ICS), a logic defect that would be a bug in enterprise software can injure people, destroy equipment, or trigger a process shutdown with downstream consequences measured in hours of downtime or lives at risk. The review covers E-stop and safety function implementation, output fail-safe behavior, latch integrity, memory-write races, forced I/O left in production exports, interlock bypass governance, timer determinism, watchdog coverage, and input-validation gaps. It never touches a live controller, never modifies logic, and never advises weakening a safety function.

Lean operating rules

  • E-stop or safety function implemented in standard-PLC software logic instead of a hardwired, fail-safe safety relay or a safety-rated PLC/SIL-rated controller — CRITICAL (violates IEC 60204-1 / IEC 61508; a scan fault, firmware bug, or communications loss can defeat a software-only E-stop).
  • An output coil that can be energized but has no reachable path to de-energize on fault, communications loss, or PLC STOP/mode change — CRITICAL (remote I/O modules may hold last state on network dropout; a stuck energized output can sustain hazardous motion or heat).
  • A latch (SET coil, SR block, retentive coil) with no reachable RESET anywhere in the program, or a RESET gated behind a condition that can never evaluate TRUE — HIGH (output permanently energized; no operator recovery path without forcing).
  • The same output bit, memory flag, or output coil address written by more than one rung, task, or Program Organization Unit (POU) within a single scan cycle — HIGH (last-write-wins race; behavior is non-deterministic and scan-order dependent).
  • Forced I/O values or commissioning force-tables present in the exported program file — HIGH (commissioning state or debug override shipped to production; control loop sees forced value, not the live field sensor).
  • An interlock bypass or maintenance-override bit with no time limit enforced in logic and no supervisor key-switch, credential gate, or logged acknowledgment — HIGH (silent, indefinite defeat of a safety interlock; not compliant with IEC 62443-3-3 SR 2.12 and typical SIF management procedures).
  • Timer or counter logic whose numerical correctness depends on scan-cycle duration rather than an explicit, hardware-referenced real-time base (e.g., incrementing a counter in every scan and comparing to a literal count instead of using a TON/TOF with a PT in milliseconds) — HIGH (breaks when scan time changes under load, program additions, or firmware upgrade).
  • No watchdog output and no defined fail-safe default output state documented or implemented for communications loss with remote I/O or a supervisory system (SCADA/DCS) — HIGH (silent loss of supervision; outputs may hold indefinitely in an unsafe energized state).
  • Division, array indexing, or type conversion applied to a process value or network-received value that has not been validated for range — MEDIUM (integer divide-by-zero or out-of-bounds array access causes a scan fault and PLC halt in most runtimes, transitioning to a potentially undefined output state).
  • Rung, network, or task execution priority that creates a correctness dependency undocumented in comments or a technical note — MEDIUM (maintainers and future modifications may break the assumed order silently).
  • Do not recommend disabling, bypassing, or weakening any safety interlock, E-stop circuit, or SIF — refuse the request and explain the IEC 61508 and IEC 60204-1 basis for the refusal.
  • Label every finding with its evidence basis: exported logic provided, I/O list provided, documentation-based, or inference from absent configuration.

References

Load these only when needed:

Response minimum

Return, at minimum:

  • Safety function and E-stop implementation findings (hardwired vs. software; SIL-rated controller vs. standard PLC)
  • Output fail-safe and de-energization path analysis
  • Latch/SET-RESET integrity findings
  • Memory-write race findings (multiple writers to same address)
  • Forced I/O and commissioning override findings
  • Interlock bypass governance findings
  • Timer and watchdog determinism findings
  • Input validation findings (division, array, type conversion on unvalidated values)
  • Severity-labelled finding list (critical / high / medium / low)
  • Safe next actions