Systematic diagnostic workflow for Sigenergy ESS inverter issues. Walks through running state → alarms → power flow → battery health → EMS mode → energy trends with common issue patterns and likely causes. Use when the user reports something wrong, alarms, battery not charging/discharging, low PV production, inverter errors, off-grid events, or connectivity problems.From its SKILL.md
npx -y skills add paulczar/sigen-mcp --skill sigen-diagnoseAssembled from the repository path, not quoted from the project. Check it against their README if it does not work.
One thing to look at
- 1 stars1 stars. Stars are a popularity signal and not a quality one, but at this level it is likely that nobody has read this closely except its author, and you would be relying on your own review.
SKILL.md
4.3 KB, as published. Nobody here has run it
sigen-diagnose — Inverter Diagnostic Workflow
Step-by-step diagnostic procedure for investigating issues with the Sigenergy ESS system. Designed for systematic troubleshooting rather than quick status checks.
Prerequisites
sigen-mcpMCP server must be connected- User should describe the observed symptom if possible
Procedure
Step 1: Check Running State
Call read_plant and look at:
- Running State: Should be
Running (1). IfFault (2),Shutdown (3), orStandby (0), there's an operational issue. - Grid Status: If
OffGrid(Auto)orOffGrid(Manual), the inverter is islanded from the grid.
→ Grid goes off-grid during:
- Grid outage / blackout
- Grid voltage/frequency outside limits
- Manual islanding (e.g., for backup mode)
Step 2: Decode Active Alarms
Call read_alarms. If alarms are active:
- Cross-reference with the register definitions in
registry.ts(alarm code appendices 2–13) - PCS alarms (Appendix 2-3): Inverter hardware issues (grid fault, insulation, temperature, DC bus)
- ESS alarms (Appendix 4): Battery issues (SOC low, temp, comms, cell voltage)
- Gateway alarms (Appendix 5): Communication or system-level issues
- DC Charger alarms (Appendix 11): EV charging issues
- Plant alarms (Appendix 12-13): System configuration or sensor issues
Step 3: Check Power Flow
Call read_inverter_detail looking for anomalies:
| Symptom | What to Check |
|---|---|
| Low PV | PV string V/I readings — compare multiple strings. If one string is 0V while others produce, that string may be faulted |
| Battery not cycling | ESS Power ~0 kW despite PV available. Check if EMS mode is correct. Check read_plant for grid status |
| Export unexpectedly high/low | Plant active power vs PV generation vs ESS power vs load |
| Inverter tripping | Running state, internal temp, frequency — may be grid fault |
Step 4: Check Battery Health
Call read_battery_status or extract from read_plant:
- SOC vs SOH: Rapid SOC changes with low SOH suggests battery degradation
- Temperature: If battery temp > 45°C or < 0°C, performance may be limited
- ESS Power Availability: In
read_plant, compare current ESS power with available max charge/discharge
Step 5: Check EMS Mode
Call read_ems_mode:
- 0 (MaxSelfConsumption): Self-consumption priority — charges battery from PV excess, discharges when load > PV
- 1 (AI): Cloud-optimized mode
- 2 (TOU): Time-of-use — follows configured schedule
- 5 (FullFeedIn): All PV to grid, no self-consumption
- 9 (Custom): Custom parameters
If the system isn't behaving as expected, the EMS mode may be wrong. Check with the user what mode they expect.
Step 6: Check Energy Accumulators
Call read_plant_energy to look at trends:
- Zero PV generation on a sunny day → Possible inverter/panel issue
- Unbalanced import/export → May indicate meter wiring issue or CT clamp problem
- EV energy vs expected → DC charger may not be working (check Step 3)
Common Issue Patterns
| Pattern | Likely Cause | Action |
|---|---|---|
| OffGrid + no alarms | Grid outage | Wait for grid restoration or check grid connection |
| OffGrid + PCS alarms | Grid fault (V/Hz outside limits) | Check grid quality, may need electrician |
| Running but 0 PV | Night time, or PV string fault | Check PV string voltages. If 0V on all strings → night. If 0V on one string → fault |
| Battery stuck at SOC | Hit charge/discharge limit | Check if set_charge_limit / set_discharge_limit set too low |
| Export > PV + Battery | Impossible — indicates measurement error | CT clamp may be misconfigured |
| Temperature > 65°C | Overheating | Check fan operation, ambient temp, ventilation |
| "Illegal data address" errors | Register not supported on this firmware | Expected for optional registers, not an issue if tools handle gracefully |